<ArticleTitle>Optimal design of a microgrid based on economic, pollution, and reliability aspects for remote rural areas</ArticleTitle>
<VernacularTitle></VernacularTitle>
			<FirstPage></FirstPage>
			<LastPage></LastPage>
			<ELocationID EIdType="pii">4009</ELocationID>
			
<ELocationID EIdType="doi">10.22044/rera.2026.17535.1519</ELocationID>
			
			<Language>EN</Language>
<AuthorList>
<Author>
					<FirstName>Alireza</FirstName>
					<LastName>Babajani</LastName>
<Affiliation>Department of Electrical and Biomedical Engineering, Mazandaran University of Science and Technology, Babol, Iran</Affiliation>

</Author>
<Author>
					<FirstName>Ali</FirstName>
					<LastName>Ghasemi-Marzbali</LastName>
<Affiliation>Department of Electrical and Biomedical Engineering, Mazandaran University of Science and Technology, Babol, Iran</Affiliation>

</Author>
</AuthorList>
				<PublicationType>Journal Article</PublicationType>
			<History>
				<PubDate PubStatus="received">
					<Year>2026</Year>
					<Month>02</Month>
					<Day>21</Day>
				</PubDate>
			</History>
		<Abstract>Abstract- This study develops an optimal sizing framework for a standalone photovoltaic–wind–diesel–battery microgrid intended for remote residential applications. Photovoltaic generation, wind generation, diesel backup, and battery storage are sized simultaneously under two loss of power supply probability (LPSP) limits of 2% and 5% to quantify the cost–reliability trade-off. The sizing problem is solved using the Bald Eagle Search (BES) algorithm and compared with particle swarm optimization (PSO) and a genetic algorithm (GA). Under the reported simulations, BES yields the lowest objective value in both reliability scenarios. At LPSP = 2%, the BES objective value is 7.44% lower than that obtained using PSO and 5.44% lower than that obtained using GA. Tightening the reliability requirement from LPSP = 5% to 2% increases the reported system cost by approximately 9% and requires greater renewable-generation and battery-storage capacity. Batteries represent approximately 29–33% of the reported total cost. First-order cost-share estimates further indicate that the total cost is more sensitive to changes in battery-related costs than to variations in diesel-related costs when the optimized component capacities are held fixed.</Abstract>
		<ObjectList>
			<Object Type="keyword">
			<Param Name="value">Standalone microgrid</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">Hybrid renewable energy system</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">Optimal sizing</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">Loss of power supply probability</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">Bald Eagle Search algorithm</Param>
			</Object>